Estimate sump-pump runtime from the water—not the horsepower.
Enter the pump's measured running watts, observed seconds per cycle, and wet-weather cycles per hour. The calculator converts that behavior into average load, estimates station runtime, and checks the output ratings you enter against the pump's running and startup requirements.
Affiliate disclosure: Power Prep Labs may eventually earn a commission from clearly labeled shopping links, at no extra cost to you. No paid links are currently active.
Estimate runtime and rating headroom
The defaults are an illustrative 800 W pump running for 45 seconds, 20 times per hour—a 25% duty cycle. They are not specifications for a particular pump. Replace every value with evidence from your installation.
Planning estimate only. A published surge number does not prove motor-start compatibility. Confirm the exact pump and station manuals, voltage, waveform, grounding, GFCI behavior, cable ratings, environmental limits, and real startup behavior.
Current stations that clear the energy and continuous-output screen
0 of 27 source-dated models meet the calculated rated-capacity target and entered running load. Published surge is shown separately and is not treated as a compatibility guarantee.
Affiliate disclosure: Power Prep Labs may eventually earn a commission from clearly labeled shopping links, at no extra cost to you. Paid relationships never affect this filtering or capacity-first order. No paid links are currently active.
| Model | Capacity | AC output | Published surge | Weight | Primary source | Shop |
|---|---|---|---|---|---|---|
| Loading source-dated model data… | ||||||
Models are filtered only by the calculated energy target and continuous-output threshold, then ordered by capacity; the table shows the first eight. Voltage, waveform, ports, grounding, GFCI behavior, cable requirements, transfer equipment, environmental limits, and real motor startup still require separate verification.
The formulas
duty cycle = seconds per cycle × cycles per hour ÷ 3,600average watts = running watts × duty cycleplanning energy = rated Wh × efficiency × (1 − reserve)runtime hours = planning energy ÷ average wattsrated capacity needed = average watts × target hours ÷ efficiency ÷ (1 − reserve)Why horsepower is not enough
Nominal horsepower does not identify the exact electrical load. Current manufacturer documents illustrate the problem: Liberty lists its 115 V, 1/3 HP Model 257 at 5.2 full-load amps and 8 locked-rotor amps, while Zoeller lists its 115 V, 3/10 HP M53 at 9.7 amps. Those figures are not interchangeable with measured watts, but they demonstrate why the exact nameplate, manual, and startup evidence matter.
Measure the condition you need to survive
- Confirm that the measuring equipment is properly rated for the pump and motor startup.
- Record running watts after startup, seconds from switch-on to switch-off, and cycles per hour during representative wet-weather inflow.
- Repeat during a more demanding condition if it can be done safely; do not manufacture a flooding hazard to create a test.
- Use the highest defensible duty cycle and keep reserve for changing inflow, inverter overhead, temperature, battery age, and measurement error.
Read the result as two separate decisions
- Energy: the estimated runtime and capacity target describe how long the measured cycle could continue.
- Output: continuous and surge comparisons only screen the ratings entered. They do not guarantee the inverter will start the motor.
- Failure consequence: a positive calculation does not replace an alarm, secondary pump, water-powered backup where appropriate, generator plan, or human response.
Move from the pump to a complete outage plan
Use the five-layer basement flood planner to separate drainage, primary pumping, independent backup pumping, emergency energy, and detection plus response before treating a runtime result as a plan.
If a refrigerator, freezer, internet equipment, or lights will share the station, size the simultaneous loads and the largest motor-start event together. The combined plan exposes the extra running load present when the pump starts.
Open the editable sump-pump + refrigerator plan → Load the combined plan and filter current stations →Compare local and remote water-leak alarms as a separate detection layer; an alarm does not power the pump or remove water.